15) Troubleshooting CH61, CH62
61
62
Condenser pipe sensor
temp. high
Heat sink sensor
temp. high
• Condenser pipe sensor
detected high
temp.(65°C)
• Heat sink sensor detect-
ed high temp.(95°C)
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
• Check the fan is locked.
• Check the sensor of heat sink.
Display
code
Title Cause of error Check point & Normal condition
Check Point
• CH 61
1. Check the install condition for over load.
(Refrigerant, Pipe length, Blocked, …)
• CH 62
1. Check the fan is locked.
2. Check the sensor of heat sink.
COMP
Hz
95°C
70°C
80°C
5Hz
Down
5Hz
Down
OFF
OFF OFF
FAN ON
Heat Sink Temp
NormalNormal
50°C
55°C
restart