5. Electric Characteristics
Inverter SINGLE A
- 75 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Unit
Model Type MCA MOP MSC RLA kW FLAVoltage
Voltage range
Hz
Power Compressor OFM
AUUW368C1
[UU37WE]
AUUW368C
[UU37W UEC]
AUUW428C
[UU43W UHC]
AUUW488C
[UU49W UHC]
AUUW608C
[UU61W UHC]
7.76 21.1 14 7 0.13 1.4
9.12 26.0 14 7 0.18 1.5
10.99 29.7 14 7 0.18 1.5
11.00 35.0 14 7 0.18 1.5
inverter
50
380~415
Min : 352
Maxi :457
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the mini-
mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Select proper circuit breaker as given below
MCA < circuit breaker ≤ MOP
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
7. MSC & RLA are measured as the compressor only test condi-
tion.
8. MSC values
14 : MSC of (inv. comp.)
9. RLA is measured during each individual compressor test condi-
tion.
Ex) 7.0 : RLA of (inv. comp.)
10. OFM is measured as the outdoor unit test condition
(Example) Selection of proper circuit breaker
Model : AUUH368C
- Rated running current : 5.09 A (refer to spec. sheet)
MCA = (1.25 x Load1) + Load2 + Load3
= (1.25 x 8.75) + 0 + (1.4) = 7.76 A
MOP = (2.25 x Load1) + Load2 + Load3
= (2.25 x 8.75) + 0 + (1.4) = 12.84 A
→ Finally select circuit breaker 20A
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)