Ceiling Duct Type
- 122 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 27°C.
The operation diagram is as following.
ON
ON
Off Off
Low Low
1min1min
20°C
27°C
33°C
Indoor unit
Heat-Exchanger
temperature
Setting fan
spped
Setting fan
spped
Compressor
Outdoor fan
Indoor fan
4way Valve
ON