Inverter SINGLE A
- 78 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
7.3 Piping length and the elevation
Gas Liquid Standard Max. Standard Max
.
36k Btu/h
5/8"(15.88mm) 1/4"(6.35mm)
7.5 50 5 30 35
42k Btu/h
3/4"(19.05mm) 3/8"(9.52mm)
7.5 75 5 30 50
48k Btu/h
3/4"(19.05mm) 3/8"(9.52mm)
7.5 75 5 30 50
60k Btu/h
3/4"(19.05mm) 3/8"(9.52mm)
7.5 75 5 30 50
Capacity
Pipe Size
Length A(m) Elevation B(m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
If piping length is more than 5m
Outdoor unit
Indoor unit
B
CAUTION:
Rated performance for refrigerant line length of:7.5m
Capacity is based on standard length and maximum allowance length is on the basis of reliabili-
ty.
Improper refrigerant charge may result in abnormal cycle.
Oil trap should be installed every 10 meters.