Elba R410A Guía para resolver problemas Pagina 117

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 116
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
COMP
Outdoor fan
Indoor fan
4way valve
Setting Temperature
+2°C(Unit Sensing)
0°C(Remo Sensing)
(Thermo ON)
Setting Temperature
+4°C(Unit Sensing)
+2°C(Remo Sensing)
(Thermo OFF)
Indoor unit
Heat-Exchanger
temperature
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
ON
ON
ON
ON
Low
LowLowLow
Low
Lo
OffOffOff
ON
OFF
OFF
Low fan during 10sec
A
A
B
B
Intake Air Temperature
Compressor-off interval : - While the indoor Heat-Exchanger temperature is higher than 40°C, fan operates
at low speed, when it becomes lower than 40°C fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
40°C
33°C
30°C
27°C
20°C
Ceiling Duct Type
- 121 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Vista de pagina 116
1 2 ... 112 113 114 115 116 117 118 119 120 121 122 ... 143 144

Comentarios a estos manuales

Sin comentarios