Elba R410A Guía para resolver problemas Pagina 76

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 75
Troubleshooting Guide
- 80 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Self-diagnosis Function
Error Indicator
The function is to self-diagnosis air conditioner and express the troubles identification if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble for error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
Having or not of error code is different from Model.
Indoor Error
Error code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
00 No Error ON
01 Indoor Room themistor error 1time OFF
02 Indoor in-piping sensor error 2times OFF
03 Remote controller error 3times OFF
04 Drain Pump error 4times OFF
05 Communcation error between in and out 5times OFF
06 Indoor Out-Piping sensor error 6times OFF
07 Differnt mode operation 7times OFF
Outdoor Error
Error Code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
21 DC Peak (IPM Fault) 2times 1times Off
22 CT 2(Max CT) 2times 2times Off
23 DC Link Low Volt. 2times 3times Off
24 L/H press SW 2times 4times Off
25 Low voltage / Over voltage 2times 5times Off
26 DC Comp Position Error 2times 6times Off
32 D-Pipe High (INV) 3times 2times Off
33 D-Pipe High (Normal) 3times 3times Off
40 CT Sensor (Open / Short) 4times O Off
41 INV. D-PipeTh Error (Open / Short) 4times 1times Off
44 Outdoor Air Th Error (Open / Short) 4times 4times Off
45 Cond. Pipe Error (Open / Short) 4times 5times Off
46 Suction Pipe Error (Open / Short) 4times 6times Off
47 Const D-PipeTh Error (Open / Short) 4times 7times Off
51 Over Capacity 5times 1times Off
52 Comm. Error(Main micon <-> Sub micom) 5times 2times Off
53 Comm. Error(Indoor <-> Outdoor) 5times 3times Off
54 Outdoor 3 phase power supply
5times 4times Off
Reverse phase / phase omission
60 EEPROM Check Sum Error 6times O Off
61 Cond. Pipe High 6times 1times Off
62 Heatsink High 6times 2times Off
63 Cond. Pipe Low 6times 3times Off
65 Heatsink Th Error (Open/Short) 6times 5times Off
67 Outdoor BLDC Fan Lock 6times 7times Off
105 Comm. Error(Main board <->Fan board)
10times 5times Off
Vista de pagina 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 143 144

Comentarios a estos manuales